Megger MIT30 30 kV High Voltage Insulation Tester
- Brand
- Megger
- SKU:
- MIT30
- Availability:
- Discontinued
Megger MIT30 Offers
The Megger MIT30 is a portable 30-kV insulation tester that has been developed to undertake tests on UST (ungrounded test samples). It satisfies the demand for a variety of high voltage, high accuracy, and low current applications. The MIT30 is NOT suitable for use on grounded/earthed test samples.
The MIT30 has a test current of up to 330 µA, and user selectable trip levels from 0 to 360 µA. The MIT30 provides protection to the test piece against flashovers (arcing) and further damage in the event of a breakdown. An audible ionization indicator gives an audio indication of any electrical discharges present during the test period.
The MIT30 can be used to perform step-voltage and proof tests which, when incorporated into a routine maintenance program, can aid in predicting potential failure before breakdown occurs.
The MIT30 will operate from a wide range of input voltages and frequencies. The unit will will operate from 85-264 V ac with a frequency range of 47-440 Hz.
Applications
The MIT30 checks the electrical insulation quality and integrity of a wide variety of insulation material on UST ungrounded systems.
Due to the unique combination of up to 30-kV high voltage, high accuracy down to 100 nA, and low current 0-330 µA, the MIT30 has several applications:
- Acceptance and Maintenance Testing of Electrical Plant:
- Switchgear
- Buss-Bars
- Capacitors
- Defense Industry
- Aerospace Industry
- Rubber Safety Glove Testing
- Testing of Vacuum Interrupters
- Power Equipment/Plant Manufacturers to Perform QA/QC Production Tests
Key Features
- Ergonomic design ensures ease of use, hence subsequent reduction in instrument learning time. This allows the operator to undertake accurate safety testing in a minimum amount of time.
- Fast charging of high-capacitance samples reduces testing times.
- Current guard circuit ensures highly accurate measurements and test results, thus avoiding external interferences that could affect the accuracy of any test results.
- Highly accurate voltage and current outputs normally associated with a test bench or laboratory test set, in a rugged, field-proven case, takes high accuracy into the field environment.
- User selectable current trip points provide protection to the test piece and the operator in the event of a breakdown in the insulation of the object being tested.
- Adjustable ionization indicator gives audible indication of electrical discharges during test.
- Universal input 85-264 V ac, 47-440 Hz makes the MIT30 suitable for a wide variety of applications.
- Compact, lightweight and rugged construction makes the unit ideal for field use.
- Its rugged, field-proven case has in integrated carry handle for easy carrying and an air transport pressure relief value which allows the instrument to be safely transported without damage.
Safety and Reliability
- Fail-Safe, gravitationally invariant internal grounding switch
- Zero-Start safety provision
- Cable interlock with bright LED, visible even in direct sunlight
- Triaxial HV output cable, with integrated HV, guard, and current sense
- Detachable HV output cable, shielded with interlock provision
- Output current overload relay
- Switch control and indicating lights for high-voltage ON/OFF
- Protected output for both short/open circuit conditions
- Fused power inlet module
Specifications
Insulation ranges | |
Nominal Test Voltage | 500 V, 250 V (d.c.) |
Measuring Range | |
All instruments | 10 k½ - 999 M½ on all ranges |
Short Circuit Current | 1.5 mA nominal |
Test Current on Load | 1 mA at min. pass values of insulation (as specified in BS7671, HD 384 and IEC 364) |
Accuracy (at 20° C) | ±3%, ±2 digits |
Continuity ranges | |
Measuring Range | 0,01 ½ - 99,9 ½ (0 -50 ½ on analogue scale) |
Open Circuit Voltage | 5 V ±1 V |
Short Circuit Current | 200 - 215 mA |
Terminal Characteristics | |
Accuracy (at 20° C) | ±3% ±2 digits |
Zero Offset Adjust | 0 - 9 ½ |
Continuity Buzzer | Operates at < 5 ½ Response time <20 ms |
Voltage range | |
Measuring Range | 0 - 600 V a.c. (50/60 Hz) or d.c. |
Accuracy (at 20° C) | d.c. or a.c. (50/60 Hz) ±1%, ±2 digits |
Temperature coefficient | <0,1% per °C on all ranges. |
Default voltmeter | |
(all modes except off) | Beeps and flash V on the display |
Test inhibit | If more than 50 volts is detected, testing will be inhibited. |
Temperature and humidity | |
Operating Range | -10°C to +60°C |
Operating Humidity | 93% R.H. at +40°C max. |
Storage Range | -25°C to +70°C |
Test Result Storage (1000 results) | |
Job Number | 255 locations |
Distribution Board no. | 99 locations |
Circuits | 99 locations |
Phases | P1, P2, P3 |
Last recorded result may be recalled to the display. All data can be downloaded to a PC using Download Manager (supplied) or Megger Powersuite Professional of Windows software | |
Communications | USB interface |
Environmental Protection | IP54 |
Fuses | Terminals 500 mA (F) 600 V, 32 x 6 mm Ceramic HBC 10 kA minimum. |
Display shows if fuse is ruptured. | |
Safety | Meets the requirements of IEC61010-1 Cat III 600 V phase to earth. |
Automatic discharge | After an insulation test the item under test will be discharged automatically. Any voltage present will be indicated on the display so that the discharge can be monitored. |
Power supply | |
Battery | 8 x 1,5 V cells IEC LR6 type(AA alkaline). Rechargeable NiCd or NiMH cells may be used. Battery condition is constantly shown on the display as a four-section bargraph. |
Battery Life | 5000 consecutive tests (5 seconds per test) on any test using 2Ah batteries. Weight |
All units | 980 gms |
Dimensions | All units: 203 x 148 x 78 mm (8 x 5.7 x 3.2 inches) |
E.M.C. | In accordance with IEC61326 including amendment No.1 |
What's included with the Megger MIT30
- HV Triaxial Output Cable, 3 m
- Input Power Cord, 120 V
- Input Power Cord, 230 V
- Instruction Manual