AEMC Power & Energy Logger Model PEL 103 (w/LCD, No Sensors) {ETL}
- Brand
- Aemc
- SKU:
- 2137.62
- UPC:
- 6.85E+11
AEMC PEL 103 Description:
The design of the Logger allows it to be installed inside a load centre panel (including the current sensors) enabling the door to close on most panels. The PEL 102 offers all the essential functions for logging power/energy data from most current electrical power networks 17 network set-ups provided. Measure and record three voltage inputs and current inputs, Watts, VARS, VA and Energy (kWh and kVA). Power Factor (PF), Displacement Power Factor (DPF), Crest Factor, Frequency and THD are calculated and recorded. Individual harmonic % information from 1 to the 50th harmonic are recorded at the operator's choice. All variables are recorded and stored at a one second interval as well as user selectable demand intervals from 1 to 60 minutes.
Energy costs can be quickly and easily calculated and displayed by simply entering the unit cost for a kilowatt hour into the software. Data is stored on a removable SD card. Data can be retrieved using a Bluetooth, USB and/or Ethernet (local or internet) connection by transporting the SD card back to a PC. The comprehensive DataView? software (included) provides the ability to view data from several hundred PEL 100 series instruments on a local network or over the internet allowing the user to evaluate energy usage in a department or facility basis, a remote site, or even in a city, anywhere in the world. DataView? allows measurements to be seen in real-time on a PC and stored data to be downloaded for analysis and report generation.
Features
- Simple to use, single-, dual- (split-phase) and three-phase (Y, ?) power & energy loggers
- Provides all the necessary functions for Power and Energy data logging for 50Hz, 60Hz, 400Hz and DC distribution systems
- Current measurements from 200mA up to 10,000A using flexible current sensors
- Automatic recognition of the connected current sensors/probes
- Power measurements: VA, W and var
- Energy measurements VAh, Wh (source/load indication) and varh (including quadrant indication)
- Record cost of energy usage
- Power Factor (PF), Cos (?), Tan (?) and DPF
- Total Harmonic Distortion (THD) for voltages and currents
- Harmonics up to the 50th order for 50/60Hz voltages and currents and 7th order for 400Hz
- Simultaneous RMS measurements of each phase @ 128 samples/cycle and DC
- Bright blue, four line LCD on Model PEL 103 (3 phases shown simultaneously)
- Storage of measured and calculated values on a SD-Card or SDHC-Card
- Configuration of current and voltage ratios to external PT and CT ratios
- USB, LAN, and Bluetooth communication
- Includes DataView? software for data storage, real-time display, analysis and report generation with supplied pre-defined or custom templates
Applications
- Measure efficiency, find areas for potential savings
- Track Sub-billing occupants for energy costs
- Assign energy costs to departments or operations within a department
- Track peak demand periods and find opportunities for surcharge reductions
- Determine present capacity and circumvent unnecessary electrical expansion costs
- Verify the reliability and operation of electrical machinery
- Improve response time to solve power related problems
- Track energy availability and reliability of supply
- Reduce field service time at sub-stations
AEMC PEL 103 Specifications:
General | |
Sampling Frequency | 128 samples per cycle; 50/60Hz (16 samples/cycle 400Hz) |
Data Storage Rate | 1 per second |
Demand Period Storage Rate | User selectable (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30 and 60 minutes) |
Recorded Parameters (Single- and Poly-Phase) | V, I, W, VA, var, PF, Tan, Wh, Vah, varh, THD (V and I) Individual harmonics (from 1 through 50 per phase); Crest Factor (CF), Cos f / DPF |
Event Log | Tracks and records status changes and error messages along with recorded data |
Front Panel Indicator LEDs | Bluetooth active, recording in progress, phase connection reversal, overload, battery charging and SD Card status |
Storage Capacity | 2GB SD card (included) is used for storage. SD cards (up to 2GB); SDHC cards (4 to 32GB) formatted FAT32 are supported |
Inputs | Voltage: 3 voltage input channels via 4mm safety banana jacks Current: 3 current input channels via custom 4 pin jacks that accept AEMC? probes and sensors |
Mechanical | |
Communication Ports | USB 2.0, Ethernet (RJ45), Wireless Bluetooth Class |
Dimension/Weight | 10.08 x 4.92 x 1.46" (256 x 125 x 37mm) / <1kg |
Case / Index of Protection | Double insulated, rubber over-molded, polycarbonate UL94 V1 rated / IP54 non operating |
Mounting / Security | Embedded magnets on back side, keyhole slot on back side / Kensington anti-theft system |
Safety Rating / CE Rating | Complies with IEC 61010-1:Ed3, and IEC 61010-2-030:Ed1 for 1000V CAT III / 600V CAT IV, Pollution Degree 2 / Yes |
What's included with the AEMC PEL 103
- AEMC PEL 103 Power & Energy Logger with Display
- Small Classic Tool Bag
- 5 ft USB cable
- Four Black Test Leads and Alligator Clips
- Power Cord
- 12 Color-coded ID Markers
- Four water-tight AmpFlex? A196-18-BK
- Multifix Mounting System
- Safety Card for the PEL
- Sensor Compliance Sheet
- 2 GB SD-Card with USB-SD-Card Reader
- Quick Start User Guide