Megger MIT481/2 Description
Features
- Insulation testing up to 500 V and 100 GΩ range in a hand held instrument
- 3 wire connection for A, B and E (Tip, Ring and Earth) connection
- Gated access to 500 V to prevent accidental damage
- Rechargeable options for mains and car charging
- Single range, faster continuity testing from 0.01 Ω to 1 MΩ
- Differential measurement capability
- Stabilized insulation test voltage
- 600 V TRMS AC and DC voltage measurement
- Test result storage and Bluetooth downloading
- CAT IV 600 V and IP 54
SPECIFICATION
Insulation | |
Nominal Test Voltage | 50 V, 100 V, 250 V, 500 V |
Accuracy | 50 Volts 10 GΩ ± 2% ± 2 digits ± 4% per GΩ 100 Volts 20 GΩ ± 2% ± 2 digits ± 2% per GΩ 250 Volts 50 GΩ ± 2% ± 2 digits ± 0.8% per GΩ 500 Volts 100 GΩ ± 2% ± 2 digits ± 0.4% per GΩ |
Display Range | Analog: 1 GΩ full scale |
Resolution | 0.1 kΩ |
Short Circuit/Charge Current | 2 mA + 0 to 50% to EN61557-2 (2007) |
Open Circuit Voltage Insulation | -0% +2% ± 2 V |
Test Current | 1 mA at min. pass value of insulation to a maximum of 2 mA maximum EN61557 Operating range: 0.10 MΩ to 1 GΩ |
Leakage Current | 10% ±3 digits |
Continuity | |
Range | 0.01 Ω to 1 M Ω |
Accuracy | ± 3% ± 2 digits (0 to 100 Ω) ±5% ±2 digits (>100 Ω to 500 kΩ) (>500 kΩ to 1 MΩ unspecified) Service Error: BS EN 61557-4 (2007) - ± 2% 0.1 to 2Ω ± 6.8% |
mA Range | |
DC | 0.0 mA - 500 mA ±5%, ±2 digits |
AC | 0 to 10 mA: unspecified 10 to 500 mA: ±5%, ±2 digits (15 to 400 Hz sinusoidal) |
Voltage | |
Range | AC: 10 mV to 600 V TRMS Sinusoidal (15 to 400 Hz) DC: 10 mV to 600 V |
Range Accuracy | AC: ± 2% ± 2 digits DC: ± 2% ± 2 digits Service Error: BS EN 61557-1 (2007) - ± 2.0% ± 2d 0 V to 300 VAC/DC ± 5.1 |
Frequency Measurement | |
Range | 15 to 400 Hz |
Accuracy | ± 0.5% ± 1 digit |
General Specifications | |
Temperature | Operating: 14 to 131°F (-10 to 55°C) Storage: -13 to 158°F (-25 to 70°C) |
Humidity | 90% RH at 104°F (40°C) |
Maximum Altitude | 6560' (2000 m) |
Dimensions | 9 x 4.25 x 2.32" (2.28 x 108 x 63 mm) |
Weight | 1.76 lbs (800 g) |
Three terminal connection
Three terminal measurement permits the connection of all three test leads for A, B and E (or tip, ring and ground). The measurement pair is selected from the A-B-E (T-R-G) button on the front panel. Selection is confirmed in the display. No disconnection of test leads to measure individual pairs are required.
Alternatively the units can be used as a conventional two terminal instrument.
Insulation resistance testing
The feedback controlled insulation test voltage is now accurate to +2% -0% compared to the original +20%, providing a more accurate test voltage without the risk of over-voltage damage to circuits.
A variable range allows the exact test voltage to be selected from 10 V up to 500 V.
Applications
- Telecommunications
- Cable TV