Megger 1004-745 MIT2500-LG2 (EN ES PT IT) Insulation and Continuity tester 50/100/250/500/1000/2.5kV + Guard+ Variable voltage + PAR/PI + Storage & Bluetooth? Download with Language Group LG2 - English, Spanish, Portuguese and Italian
- Brand
- Megger
- SKU:
- 1004-745
- Availability:
- In Stock
- Model No:
- MIT2500 (2.5 kV)
Megger MIT2500 Description
Features
- Insulation testing up to 2.5 kV and 200 GΩ range in a hand held instrument
- Guard terminal for high resistance accuracy
- Adjustable insulation test voltage from 50 V to 2500 V
- Stabilized insulation test voltage
- Rechargeable options for mains and car charging
- Single range, faster continuity testing from 0.01 Ω to 1 MΩ
- Polarization Index (PI) & Dielectric Absorption Ratio (DAR)
- CAT IV 600 V applications
- Polarization Index (PI) & Dielectric Absorption Ratio (DAR)
- CAT IV 600 V applications
Functions
- Continuity buzzer limit alarms
- Insulation buzzer limit alarms
- Insulation LOCK
- Insulation test timer duration
- Backlight ON duration
- Sleep timer
- Continuity test currents
- Factory reset
SPECIFICATION
Guard terminal performance | <5% error at 500 kΩ parallel circuit resistance with 100 MΩ load |
Display Range | Analog: 1 GΩ full scale |
Resolution | 0.1 kΩ |
Short circuit/charge current | 2 mA +0% -50% to EN61557-2 (2007) [except 2500 V] |
Terminal voltage accuracy | -0% +2% ± 2 V |
Test current | 1 mA at min. pass value of insulation to a maximum of 2 mA max |
Operation | EN61557 : 0.10 MΩ to 1.0 GΩ |
Leakage current | 10% ±3 digits |
Display voltage | ±3 ±2 digits ±0.5% of rated voltage |
Timer control | Countdown timer 60 second (adjustable to 10 minutes) |
Dimensions | 9.00 in x 4.25 in x 2.32 in (2.28 mm x 108 mm x 63 mm) |
Weight | 1.8 lb (815 g) |
Applications
- Commercial Avionics
- Military Land, Marine and Air communications
- Manufacturing/production line goods
- Electrostatic measurement
- Component testing
- Battery powered traction and lifting equipment
Insulation Resistance Testing
The feedback controlled insulation test voltage is now accurate to +2% -0% compared to the original +20%, providing a more accurate test voltage without the risk of over-voltage damage to circuits.
A variable range allows the exact test voltage to be selected from 50 V to 999 V in 1 V steps, (1kV to 2.5 kV in 10 V steps) providing 1100 test voltage options.
Variable Insulation Voltage (NEW)*
The variable mode provides a unique solution for awkward insulation voltage measurement applications. The range option allows an insulation test voltage from 50 V to 999 V in 1 V steps, 1.0 KV to 2.5 KV in 10 V steps.
Storage and Downloading Results
Revised Bluetooth® and pairing procedures have made the MIT2500 far easier to pair and download data. The test results are downloaded to a CVS file which can then be opened as an Excel spreadsheet.
Safety
Designed to be exceptionally safe to use, fast detecting circuitry prevents damage to the instruments: live circuits or across phases. Specifically, all instruments:
- Meet the international requirements of IEC61010 and EN61557.
- Live circuit detection inhibits insulation testing on circuits above 25, 30, 50, 75 or 100 V default (50 V).
- Live circuit detection and test inhibit on continuity measurements.
- Default display of live circuit voltage on all ranges.
- Detection and inhibit functions even if the protection fuse has failed.
- Suitable for use on CAT IV applications and supply voltages to 600 V.