Megger DET14C Digital Clamp-On Ground Resistance Tester with Onboard Memory
$2,205.00
- Brand
- Megger
- SKU:
- 1000-761
- Availability:
- In Stock
- Model No:
- DET14C
Megger EDT14C Description
Ensuring the job is a breeze, users can easily avoid dirt build-up thanks to the clamp's flat core ends and use the built-in filter function offering increased noise immunity in electrically noisy environments. Operation in dark and restricted areas is facilitated by a display with a backlight and an audible tone associated with the hold key.
Features
- Elliptical clamp shape improves access to earth cables and straps up to 1.9 " (50 mm)
- Low maintenance flat jaw interface
- Measures ground resistance from 0.05 to 1500 Ω
- Measures true RMS ground leakage current from 0.5 mA RMS to 35 A RMS
- CAT IV 600 V safety rating
- Auto-current measurement safety feature
- Memory to record and view results
- Automatic self calibration
- Auto-ranging
- High and low alarms
- Real time clock for date and time stamping of results
- Backlit LCD
Megger DET14C Specifications
Ground Resistance | |
0.05 to 0.99 Ω | Resolution: 0.01 Ω Intrinsic range: ±1.5% ±0.05 Ω |
1.00 to 9.99 Ω | Resolution: 0.01 Ω Intrinsic range: ±1.5% ±0.1 Ω |
10 to 99.9 Ω | Resolution: 0.1 Ω ±2% Intrinsic range: ±0.5 Ω |
100.0 to 199.9 Ω | Resolution: 0.1 Ω ±5% Intrinsic range: ±1 Ω |
200 to 400 Ω | Resolution: 1 Ω ±10% Intrinsic range: ±10 Ω |
400 to 600 Ω | Resolution: 1 Ω ±10% Intrinsic range: ±10 Ω |
600 to 1200 Ω | Resolution: 10 Ω Intrinsic range: ±20% |
1200 to 1500 Ω | Resolution: 10 Ω Intrinsic range: ±35% |
Current Range | |
0.5 to 0.99 mA | Resolution: 0.01 mA Intrinsic Certainty: ±2% ±0.05 mA |
1.00 to 9.99 mA | Resolution: 0.01 mA Intrinsic certainty: ±2% ±0.05 mA |
10.0 to 99.9 mA | Resolution: 0.1 mA Intrinsic certainty: ±2% ±0.1 mA |
100 to 999 mA | Resolution: 1 mA Intrinsic Certainty: ±2% ±1 mA |
1.00 to 9.99 A | Resolution: 0.01 A Intrinsic certainty: ±2% ±0.01 A |
10.0 to 35.0 A | Resolution: 0.1 A Intrinsic certainty: ±2% ±0.1 A |
Alarm Settings | |
Threshold 1 | Range: 1 to 1500 Ω Resolution: 1 Ω |
Threshold 2 | Range: 1 to 1500 Ω Resolution: 1 Ω |
General Specifications | |
Range | Selection: Automatic within each mode |
Sampling Time | <1 second |
Function | Hold: Yes with visual indicator Alarm: Yes with visual indicator |
Alarm/Warning | Buzzer: Yes |
Temperature Range | Operating: -4 to 122°F (-20 to 50°C), <85% RH Storage: -40 to 140°F (-40 to 60°C), <75% RH |
Maximum Jaw Opening | 1.5" (39 mm) |
Maximum Jaw Inner Dimensions | 1.5 x 2.16" (39 mm x 55 mm) |
IP Rating | IP30 with jaws closed |
Safety | EN 61010-2-032 CATIV 600 V Pollution degree 2 |
EMC | Class B Compliant, IEC 61326, BSEN 61326 |
Dimensions | 9.7 x 4.4 x 1.9" (248 x 114 x 49 mm) |
Weight | 2.17 lbs (985 g) |
Applications
- Buildings, pylons and RF transmitter sites without system disconnection
- Inspection and verification of lightning protection systems
- Any installation where a current loop can be generated