Megger MIT515-US Insulation Tester, 10 Teraohms Resistance, 5kV Multi-Range Test Voltage 1001-936
$4,765.00
- Brand
- Megger
- SKU:
- 1001-936
- Availability:
- In Stock
- Model No:
- MIT515-US
Megger MIT515 Description
Features
- Industry best guard terminal accuracy
- Smaller size and lightweight allows easier transport and use without compromising performance
- Compact and lightweight for easy transport and use
- Auto IR, DAR and PI
- Unique dual case design provides additional user protection
- Lithium-ion battery - extended capacity, rapid charge
- Advanced memory with time/date stamp
- CATIV 600V safety rating on all terminals
Megger MIT515 Specifications
Analog Insulation Range | 100 kΩ to 10 TΩ |
Digital Insulation Range | 10 kΩ to 10 TΩ |
Test Voltages | 250 V, 500 V, 1000 V, 2500 V, and 5000 V |
User Defined Test Voltages | 100 V to 1 kV in 10 V Steps 1 kV to 5 kV in 25 V Steps |
Accuracy (23°C) | ±5% to 1 TΩ, ±20% to 10 TΩ |
Voltage Output Accuracy (0 to 30°C) | 4 to 0% ±10 V of nominal test voltage at 1 GΩ load |
Voltmeter Range | 30 to 660 V ac or dc, 50/60 Hz Accuracy: ±3% ±3 V Frequency Range: 45 Hz to 65 Hz |
Short Circuit Current | 3 mA Nominal, Max. Power on All Loads Outperforming Many 5 mA Testers |
Insulation Alarm | 100 kΩ to 1 GΩ |
Current Measurement | Range: 0.01 nA to 6 mA Accuracy: ±5% ±0.2 nA at All Voltages |
Capacitance Range Above 500 V | 10 nF to 25 µF (Dependent on Measurement Voltage) Accuracy (23°C): ±10% ±5 nF |
Capacitor Charge | <3 s per µF at 3 mA to 5 kV |
Capacitor Discharge | <250 ms/µF to Discharge from 5000 V to 50 V |
Timer Range | Up to 99 Minutes, 15 Seconds Minimum Setting |
Memory Capacity | 5 1/2 Hours Continuous Logging Every 5 Seconds or 33 Logged PI Tests or 350 Logged IR Tests |
Industry-Standard Tests | IR, IR(t), DAR, PI |
Interface | USB Type B (Device) |
Real Time Output | USB, 1 Reading/Second (Voltage, Current and Resistance) |
Interference Rejection | 1 mA per 250 V up to a maximum of 3 mA |
Guard Terminal | 2% Error Guarding 500 kΩ Leakage with 100 mΩ Load |
Voltage Input Range | 85 to 265 V, 50/60 Hz, 60 VA |
Battery Type | Lithium-Ion, 11.1 V, 5.2 A Hour, Meets IEC 62133:2003 |
Battery Life | Typical Capacity 6 Hours Continuous at 5 kV with a 100 MW Load |
Battery Charge Time | 2.5 Hours from Deep Discharge, 2 Hours Normal Discharge 30 Minutes Quick Charge: 1 Hour Operation at 5 kV, 100 MW |
Safety | Meets the Requirements of IEC61010-1 CAT IV 600 V Default Voltmeter Warns Operator of Applied Voltage Above 50 V |
EMC | Meets the requirements of IEC61326-1 |
Ingress Protection | IP65 (Lid Closed) IP40 (Lid Open) |
Temperature Range | Operating: -4 to 122°F (-20 to 50°C) Storage: -13 to 149°F (-25 to 65°C) |
Humidity Range | 90% RH @ 104°F (40°C) |
Altitude | 3000 m, CAT rating maintained >2000 m* (*test load connected) |
Dimensions | 12 x 11 x 7" (315 x 285 x 181 mm) |
Weight | 10 lb (4.5 kg) |
Applications
- Testing the Insulation of High or Low Voltage Electric Equipment
- Generators
- Motors
- Transformers
- Cables
- Switchgear
- High-Voltage Power Cables
- High-Voltage Buses
- Large Motor/Generator Windings
- Line and Substation Transformers
- Spot Tests
- Stepvoltage Tests
- Dielectric Discharge Tests
- Ramp Tests
- Dielectric Absorption Tests
- Acceptance Testing at Installation to Check Conformance to Specifications
- Routine Preventive/Predictive Maintenance Testing After Installation
- QA Testing as Part of the Manufacturing Process
- Diagnostic Testing to Isolate Faulty Components for Repair
- Rotating Machinery
- Insulation Resistance of Armature and Field Windings