Testo 0560 0420 testo 420 Differential Pressure Instrument (-120 to 120Pa/ +/-0.480"WC)
- Brand
- Testo
- SKU:
- 0560 0420
- Availability:
- In Stock
Description
Use the testo 420 differential pressure measuring instrument to carry out simple, efficient tests on filters. You can also use the measuring instrument in conjunction with a Pitot tube to measure flow velocity and volume flow really easily in ventilation ducts.
Product Description
The testo 420 differential pressure measuring instrument is suitable for accurate differential pressure measurement up to 120 Pa, e.g. when checking filters in HVAC systems. Flow velocity and volume flow are calculated by the testo 420. The measuring instrument can also be used for absolute pressure measurement.
Differential pressure measuring instrument with practical functions
You can use a Pitot tube and compatible connection hoses (both optional) to measure the flow velocity and volume flow in ventilation ducts. Timed and multi-point mean calculation, as well as the combination of the two, along with simple input of the duct geometry provide you with support for measurements in ducts.The automatic zeroing ensures higher accuracy for low pressures. All measuring values are easy to read on the large display which has an illumination function.
Documenting the measurement data
Measurement data can be stored in the differential pressure measuring instrument for analyses and documentation. It's easy to manage the measurement data on the PC without any additional software, via the plug & play function.
Differential pressure measurement, e.g. to check filters in air conditioning and ventilation systems
Calculate flow velocity and volume flow using a Pitot tube
Handy instrument featuring a large display and user-friendly menu guidance
Save measurement data for analysis and documentation
Specification
Measuring range | -120 to +120 Pa+0.1 to +14 m/s |
Accuracy | ±2 % of mv + 0.5 Pa at +22 °C, 1013 hPa |
Resolution | 0.001 Pa0.01 m/s |
Reaction time | 1 s (t90) |
Absolute Pressure | |
---|---|
Measuring range | 700 to 1100 hPa |
Accuracy | ±3 hPa |
Resolution | 0.1 hPa |
Reaction time | 1 s |
General technical data | |
Storage temperature | -20 to +60 °C |
Dimensions | 150 x 85 x 35 mm |
Operating temperature | -5 to +50 °C |
EU-/EG-guidelines | EU-guideline 2014/30/EU |
Warranty | 2 years |
Battery type | Alkali manganese, mignon, type AA |
Battery life | 40 h |
Display size | 3.5" |
Display function | Dot matrix |
Display ligthing | with illumination |
Interface | Micro-USB |
Memory | 2 GB (internal) |