Product Description
Ground Resistance Tester Model 6417
The Ground Resistance Tester Model 6417 measures ground rod and grid resistance and impedance without the use of auxiliary rods. Clamp-on ground resistance testers can be used in multi-grounded systems without disconnecting or de-energizing the ground system under test. The Model 6417 simply clamps around the grounding electrode or conductor and measures the resistance to ground. By performing measurements on intact ground systems, the user also verifies the quality of the grounding connections and bonds. Resistance and continuity of grounding loops around pads and buildings may also be measured.
Ground Tester | Ground Rod Tester | Earth Ground Tester | Ground Continuity Tester | Ground Wire Tester
Ground Resistance Tester Model 6417
Ground Resistance Measurement (Auto-Ranging 1 to 199Ω) | ||
Measurement Range | Resolution | Accuracy |
0.010 to 0.099Ω | 0.001Ω | ±(1.5%Reading +0.01Ω) |
0.10 to 0.99Ω | 0.01Ω | ±(1.5%Reading +0.02Ω) |
1 to 49.9Ω | 0.1Ω | ±(1.5% Reading +0.1Ω) |
50.0 to 99.5Ω | 0.5Ω | ±(2% Reading +0.5Ω) |
100 to 199Ω | 1Ω | ±(3% Reading +1Ω) |
200 to 395Ω | 5Ω | ±(5% Reading +5Ω) |
400 to 590Ω | 10Ω | ±(10% Reading +10Ω) |
600 to 1150Ω | 50Ω | 20% approx. |
1200 to 1500Ω | 50Ω | 25% approx. |
Alarm | Adjustable from 1 to 199Ω | |
Frequency Selection | Choice of 50, 60, 128, or 2083Hz for impedance calculation | |
Maximum Overload | Permanent current: 100 max. 50/60Hz Transient current: (<5s) 200A 50/60Hz |
|
Current Measurement Range (Auto-Ranging) | ||
Measurement Range | Resolution | Accuracy |
0.200 to 0.999mA | 1µA | ±(2% Reading +50µA) |
1.000 to 2.990mA | 10µA | ±(2% Reading +50µA) |
3.00 to 9.99mA | 10µA | ±(2% Reading +50µA) |
10.00 to 29.99mA | 100µA | ±(2% Reading +100µA) |
30.0 to 99.9mA | 100µA | ±(2% Reading +100µA) |
100 to 299.9mA | 1mA | ±(2% Reading +1mA) |
0.300 to 0.990A | 1mA | ±(2% Reading +1mA) |
1.000 to 2.999A | 10mA | ±(2% Reading +10mA) |
3.00 to 39.99A | 10mA | ±(2% Reading +10mA) |
Loop Inductance Measurement | ||
Measurement range | Resolution | Accuracy |
10 to 100µH | 1µH | ±(5% Reading +1µH) |
100 to 500µH | 1µH | ±(3% Reading +1µH) |
Contact Voltage (Touch Voltage) Calculated | ||
Measurement range | Resolution | Accuracy |
0.1 to 4.9V | 0.1V | ±(5% Reading +0.1V) |
5.0 to 49.5V | 0.5V | ±(5% Reading +0.5V) |
50 to 75.0V | 1V | ±(10% Reading +1V) |
General Features | ||
Display | OLED, 152 segments 48x39mm | |
Memory | 2000 measurements | |
Communication | Bluetooth, DataView software included | |
Alarm | 3 separate alarms (Ω, V and A) | |
Power Source | 4x1.5V LR6 (AA) alkaline batteries or 4 NiMH batteries | |
Battery Life | 12 hours or 1440 30-seconds tests approx. | |
Jaw Opening | 1.38” (35mm) max | |
Dimensions | 2.16 x 3.74 x 10.31” (55 x 95 x 262mm) | |
Weight (with Battery) | 2.06 lbs (935g) | |
Operating Temperature | -4° to +131°F (-20 to +55°C) | |
Storage Temperature | -22° to +158°F (-30 to +70°C) | |
Relative Humidity | Up to 90% @ 40°C | |
Ingress Protection (IP) | IP 40 | |
EMC | EN 61326-1 | |
Safety Compliance | IEC 61010-1, EN 61010-2-30, EN 61010-2-32, Pollution Degree 2, 600V CAT IV ![]() |